Estimated Lead Time: 6-8 Weeks
Manufacturer: Honeywell
C6097A1046
Pressure switch with manual reset, 10 in. wc min, 12 in. wc max setpoint
Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.
For use with natural gas, liquid propane (LP) gas, or air.
Diaphragm-actuated safety-limit switch.
Switch can be wired to turn on alarm.
C6097A models break control circuit at setpoint on pressure fall.
C6097B models break control circuit at setpoint on pressure rise.
Lockout with manual reset and recycle options.
Lockout models have external manual reset button.
Removable transparent cover protects scaleplate and adjusting knob.
Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
Optional switch position indicator lamp available.
IP54 enclosure standard.
Ranges: 0.4 to 5 in.wc, 3 to 21 in.wc, 12 to 60 in.wc or 1.5 to 7 psi.
Surge orifice.
Integral vent limiter on all models.
Application : Safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes
Dimensions (in.) : 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep
Dimensions (mm) : 66 mm high x 69 mm wide x 69 mm deep
Mounting : Flange Mount
Electrical Ratings : Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush
Approvals, Underwriters Laboratories Inc. : Component Listed, MP 2168-8-1
Approvals, Canadian Standards Association : File # 95329 Certificate 2632-01
Electrical Connections : Screw terminals
Contact Ratings : 120 Vac Switch Contact– 3.0 AFL, 18.0 ALR, 5.0 A resistive; 240 Vac Switch Contact– 3.0 AFL, 18.0 ALR, 5.0 A resistive
Operating Temperature Range (F) : -40 F to +140 F
Operating Temperature Range (C) : -40 C to +60 C
Approvals, Swiss RE : Acceptable
Approvals, Factory MutualJI 2D4A1.AF
Approvals, Others : CSD-1 AFB: Acceptable
Operating Range (psi) : 12 to 60 in. wc
Operating Range (kPa) : 3.0 to 15 kPa
Differential Pressure Range (psi) : max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint
Differential Pressure Range (kPa) : max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint:
Differential Type : Additive
Switch Operation : Manual Reset
Switching Action : Break on pressure fall
Shipping Weight : 1.3 Kg