Estimated Lead Time : 4-6 Weeks
Manufacturer : BECKHOFF
Part Number : EJ3202
Technology : temperature measurement (RTD)
Connection method : 2- or 3-wire (default: 2-wire)
Sensor types : Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Number of inputs : 2
Measuring range : -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors)
Resolution : 0.1 °C per digit
Measurement error/ uncertainty : < ±0.5 °C for Pt sensors Input filter limit frequency : typ. 1 kHz Conversion time : approx. 85 ms default setting, 2…800 ms configurable Distributed clocks : – Power supply : via the E-bus Current consumption E-bus : typ. 165 mA Electrical isolation : 500 V (E-bus/field potential) Special features : integrated digital filter, limit value monitoring, variable connection technology Weight : approx. 30 g Operating/storage temperature : -25…+60 °C/-40…+85 °C Relative humidity : 95 %, no condensation EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4 Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27 Protect. rating/installation pos. : IP20/see documentation Approvals/markings :CE, UL Shipping Weight : 2kg















Reviews