Estimated Lead Time: 4-6 Weeks
Part Number : IP2002-B510
Manufacturer : BECKHOFF
IP2002-B510 | Beckhoff | Fieldbus Box, 8-channel digital output, CANopen, 24 V DC, 0.5 A, M12
Shipping Weight : 2 Kg
IP2002-B510 | Fieldbus Box, 8-channel digital output, CANopen, 24 V DC, 0.5 A, M12
System data : CANopen | IPxxxx-B51x, IL230x-B51x
Number of I/O stations : 63, with repeater: 99
Number of I/O points : depending on controller
Data transfer medium : shielded copper cable, 2 x signal, 1 x CAN ground (recommended)
Distance between stations : 5,000 m 2,500 m 1,000 m 500 m 250 m 100 m 50 m 25 m
Data transfer rates : 10 kbaud 20 kbaud 50 kbaud 125 kbaud 250 kbaud 500 kbaud 800 kbaud 1 Mbaud
I/O communication types : event driven, cyclic, synchron, polling
Technical data digital outputs : IP2002-Bxxx
Number of outputs : 8
Output connections : M12, screw type
Load type : ohmic, inductive, lamp load
Nominal output voltage : 24 V DC (-15 %/+20 %)
Max. output current : max. 0.5 A per channel, individually short-circuit proof
Short-circuit current : typ. 1.5 A
Auxiliary power current : typ. 20 mA per channel
Current consumption from US(without sensor current) : see documentation
Power supply connection : feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image : 8 outputs
Electrical isolation : channels/control voltage: no, between the channels: no, control voltage/fieldbus: depends on the bus system
Technical data : IP2002-B510
Extension modules : –
Digital peripheral signals : according to I/O type
Analog peripheral signals : according to I/O type
Number of PDOs (CANopen) : 16 send and 16 receive process data objects
Additional CANopen features : life, node guarding, emergency object, variable mapping, store/restore
Configuration possibility : through KS2000 or the controller (service data objects)
Data transfer rates : automatic detection of 10 kbaud up to 1 Mbaud
Bus interface : 1 x M12 plug, 5-pin
Power supply : control voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type
Power supply connection : feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Box supply current : 45 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current : according to I/O type
Electrical isolation : control voltage/fieldbus: 500 V, control voltage/inputs or outputs: according to I/O type
Operating/storage temperature : 0…+55 °C/-25…+85 °C
Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. : IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings : CE, UL
Housing data : Standard housing
Dimensions (W x H x D) : 30 mm x 175 mm x 26.5 mm
Material : PA6 (polyamide)
Installation : 2 fixing holes 3.5 mm diameter for M3