Estimated Lead Time: 6-8 Weeks
KL3052
1-, 2-channel loop-powered input terminals 4…20 mA
Number of inputs: 2
Power supply: 24 V DC via power contacts
Signal current: 4…20 mA
Technology: single-ended
Internal resistance: 80 ? + 0.7 V
Common-mode voltage UCM : –
Resolution: 12 bit
Conversion time: ~ 1 ms ~ 2 ms
Measuring error < ±0.3 % (relative to full scale value) Surge voltage resistance: 35 V max. Electrical isolation: 500 V (K-bus/signal voltage) Current consumption power contacts: only load Current consumpt. K-bus typ. 65 mA Bit width in the process image: x 16 bit data (2 x 8 bit control/status optional) Configuration: no address or configuration setting Special features: with sensor supply Weight approx.: 70 g Operating/storage temperature: 0…+55 °C/-25…+85 °C -25…+60 °C/-40…+85 °C Relative humidity: 95 %, no condensation Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27 EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4 Protect. class/installation pos.: IP 20/variable Pluggable wiring: for all KSxxxx Bus Terminals Approvals: CE, UL, Ex, GL Shipping Weight: 1 Kg Download PDF File KL3052














Reviews