Estimated Lead Time : 1 – 10 Working days.
Manufacturer : BECKHOFF
Part Number : KL9560
Power supply unit terminal 24 V DC/24 V DC, 0.1 A
Input voltage : 24 V DC (-15 %/+20 %)
Output voltage : 24 V DC (-15 %/+5 %)
Output current : ≤ 0.1 A
Short-circuit current : approx. 0.15 A
Efficiency : approx. 85 %
Diagnostics in the process image : yes
Short-circuit proof : yes, automatic restart
Insulation voltage input/output : 500 V AC permanent load
Insulation voltage : 1,500 V AC constant load field/K-bus
Residual ripple : no data
Special features : analog voltage with electrical isolation
Weight : approx. 65 g
Operating/storage temperature : 0…+55 °C/-25…+85 °C
Relative humidity : 95 %, no condensation
Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4
Protect.rating/installation pos. : IP20/variable
Pluggable wiring : for all KSxxxx Bus Terminals
Approvals/markings : CE, UL, ATEX, DNV GL
Exmarking : II 3 G Ex nA IIC T4 Gc
Design form : compact terminal housing with signal LEDs
Material : polycarbonate
Dimensions (W xHxD) : 12 mm x 100 mm x 68 mm
Installation : on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of : double slot and key connection
Marking : labeling of the BZxxx series
Wiring : solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-section :
s*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-sectionAWG :
s*: AWG 28…14,
st*: AWG 28…14,
f*: AWG 26…16
Stripping length : 8…9 mm
Current load power contacts : Imax: 10 A
Shipping weight : 2 kg














Reviews