Estimated Lead Time : 4-6 Weeks
Manufacturer : BECKHOFF
Part Number : KM2614
Bus Terminal module, 4-channel relay output, 230 V AC, 16 A, manual/autom. operation
Load type : ohmic, inductive, lamp load
Max. output current : 16 A
Number of outputs : 4 x change-over
Operation : automatic operation/manual operation at the relay
Nominal switching voltage : 250 V AC, 30 V DC
Nominal switching current : 16 A
Electrical isolation : 1.5 kV (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III
Current consumption power contacts : –
Current consumption K-bus : typ. 15 mA
Current consumption 24 V DC : 50 mA for each active relay
Bit width in the process image : 4 outputs
Switching current : 16 A AC/12 A DC at 30 V DC
Operating cycles mech. (min.) : 5 x 106
Operating cycles electr. (min.) : 1 x 106 (1 A/250 V AC)
Lamp test, electronic ballast : max. 25 A starting current
Minimum permitted load : 5 mA at 10 V
Dimensions (W xHxD) : 99 mm x 100 mm x 62 mm
Configuration : no address or configuration setting
Special features : automatic/manual operation at the relay
Weight : approx. 250 g
Operating/storage temperature : 0…+55 °C/-25…+85 °C
Relative humidity : 95 %, no condensation
Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4
Protect.rating/installation pos. : IP20/variable
Approvals/markings : CE
Shipping weight : 2 kg