Estimated Lead Time : 4-6 Weeks
Manufacturer : BECKHOFF
Part Number : KM3701
Bus Terminal module, 1-channel analog input, differential pressure, ±100 hPa (±100 mbar)
Technology : differential pressure measurement
Number of inputs : 1 (differential pressure)
Measuring error : 3 % (relative to full scale value)
Measuring range : -100…+100 hPa (-100…+100 mbar)
Max. overload : 500 hPa (500 mbar) differential, 5000 hPa (5 bar) to ambient
Resolution : 0.1 hPa (0.1 mbar) per digit
Measuring speed : 5 ms typ.
Current consumption power contacts : – (no power contacts)
Current consumption K-bus : typ. 15 mA
Bit width in the process image : 3 byte input/output
Medium : non-aggressive gases
Operating/storage temperature : 0…+55 °C/-25…+85 °C
Relative humidity : 95 %, no condensation
Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4
Protect.rating/installation pos. : IP20/variable
Approvals/markings : CE, UL
Shipping weight : 3 kg