Estimated Lead Time : 4-6 Weeks
Manufacturer : BECKHOFF
Part Number : KS3403-0010
Number of inputs : 3 x current, 3 x voltage
Technology : 3-phase power measurement
Measured values : current, voltage, effective power, energy, cos φ, peak values U, I and P, frequency
Measuring voltage : max. 500 V AC 3~ (ULX-N: max. 288 V AC)
Resolution : 16 bit (21 bit, internal)
Measuring current : max. 1 A, via measuring transformers x A/1 A
Measurement error/ uncertainty : 0.5 % relative to full scale value (U, I), 1 % calculated value
Measuring procedure : true RMS with 64,000 samples/s
Update time : 50 ms per measured value preset, free configurable
Electrical isolation : 1500 V (K-bus/field potential)
Current consumption power contacts : – (no power contacts)
Current consumption K-bus : typ. 115 mA
Bit width in the process image : input/output: 3 x 16 bit data, 3 x 8 bit control/status
Special features : energy meter, power measurement, true RMS
Operating/storage temperature : -25…+60 °C/-40…+85 °C
Relative humidity : 95 %, no condensation
Vibration/shock resistance : conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission : conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. : IP20/variable
Pluggable wiring : for all KSxxxx Bus Terminals
Approvals/markings : CE, UL
Design form : terminal housing with pluggable wiring level
Material : polycarbonate
Installation : on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of : double slot and key connection
Marking : labeling of the BZxxx series
Wiring : spring actuation by screwdriver
Connection cross-section : s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm²
Connection cross-section AWG : s*:AWG 28…16, st*: AWG 28…16, f*: AWG 26…16
Stripping length : 9…10 mm
Current load power contacts : Imax: 10 A
Dimensions (L x W X H) : 6.8 cm x 1.2 cm x 10.0 cm
Weight : 0.075 kg
Shipping Weight : 2 Kg