Estimated Lead Time : 4 – 6 weeks.
Manufacturer: Scheinder Electric
Part number: RM17UBE16
Harmony, Modular 1-phase voltage control relay, 5 A, 1 CO, 20…80 V AC/DC
Main
Range of product : Harmony Control Relays
Product or component type : Voltage control relay
Relay type : Voltage control relay
Product specific application : For single-phase and DC supply
Relay name : RM17UBE
Relay monitored parameters
Self-powered
Overvoltage and undervoltage detection
time delay : Adjustable 0.1…10 s, 0 + 10 % on crossing the threshold
Switching capacity in VA : 1250 VA
Minimum switching current : 10 mA at 5 V DC
Maximum switching current : 5 A AC/DC
Power consumption in VA : 0…3.9 VA AC
Measurement range
20…80 V voltage AC 50/60 Hz
20…80 V voltage DC
Utilisation category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
contacts type and composition : 1 C/O
Complementary
Reset time : 1500 ms time delay
Maximum switching voltage : 250 V AC/DC
[Us] rated supply voltage : 24…48 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits : 15…100 V AC/DC
Maximum power consumption in W : 1.6 W DC
Immunity to microbreaks : 20 ms
control circuit frequency : 50…60 Hz +/- 10 %
Output contacts : 1 C/O
Nominal output current : 5 A
Maximum measuring cycle : 150 ms measurement cycle as true rms value
Hysteresis : 3 % fixed of threshold setting
delay at power up
1000 ms DC
500 ms AC
Measurement accuracy : +/- 10 % of the full scale value
Repeat accuracy
+/- 0.5 % for input and measurement circuit
+/- 1 % for time delay
Measurement error
< 1 % over the whole range with voltage variation 0.2 %/°C with temperature variation Polarity : Non reversible polarity on DC supply Quality labels : CE Overvoltage category : III conforming to IEC 60664-1 Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V conforming to IEC 60664-1
400 V conforming to IEC 60664-1
Operating position : Any position without derating
Connections – terminals
Screw terminals, 1 x 0.5…1 x 4 mm² (AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 1 x 0.2…2 x 2.5 mm² (AWG 24…AWG 12) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
Tightening torque : 0.6…1 N.m conforming to IEC 60947-1
Housing material : Self-extinguishing plastic
Local signalling
LED (green) for power ON
LED (yellow) for relay ON
Mounting support : 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability : 100000 cycles
Mechanical durability : 30000000 cycles
Operating rate : <= 360 operations/hour full load Safety reliability data B10d = 470000 MTTFd = 502.2 years Width : 17.5 mm Net weight : 0.08 kg Functionality : Overvoltage and undervoltage detection Compatibility code : RM17 Shipping Weight : 1 Kg









Reviews