Estimated Lead Time : 4 – 6 weeks.
Manufacturer : Schneider Electric
Analog input module, Modicon TM5, Composition kit of I/O(TM5SAI4PH) + term. block(TM5ACTB12) + bus base(TM5ACBM11)
Range of product :Modicon TM5
Product or component type :Analog input module
Analogue input number :4
Analogue input type :Pt 100/Pt 1000 temperature probe – 200…850 °C
Analogue input resolution :16 bits
Complementary
Device composition :Bus sub-base TM5ACBM11 | Terminal block TM5ACTB12 | I/O module TM5SAI4PH
Range compatibility :Modicon LMC058 | Modicon M258
Product compatibility :Motion controller | Logic controller
Measurement resolution :0.1 °C
Colour :White
Measurement error :< 0.037 % of full scale - 200...850 °C Pt 100/Pt 1000 25 °C Temperature coefficient :0.004 %FS/°C temperature probe Non-linearity :0.001 %FS temperature probe Type of cable :Shielded cable Isolation :No insulation between channels | 500 Vrms AC insulation between channel and bus Supply :Internal [Us] rated supply voltage :24 V DC -15...20 % Common mode rejection :> 95 dB
Local signalling :1 LED green power supply | 1 LED red power supply | 4 LEDs green input status
Current consumption :2 mA 5 V DC bus | 46 mA 24 V DC input/output
Maximum power dissipation in W :1.11 W
Marking :CE
Product weight :0.14 lb(US) (0.065 kg)
Environment
Standards :UL 508 | CSA C22.2 No 142 | IEC 61131-2 | CSA C22.2 No 213
Product certifications :GOST-R | cULus | C-Tick | CSA
Ambient air temperature for operation :32…131 °F (0…55 °C) without derating horizontal installation) | 32…140 °F (0…60 °C) with derating factor horizontal installation) | 32…122 °F (0…50 °C) vertical installation)
Ambient air temperature for storage :-13…158 °F (-25…70 °C)
Relative humidity :5…95 % without condensation
IP degree of protection :IP20IEC 61131-2
Pollution degree :2 IEC 60664
Operating altitude :0…2000 m
Storage altitude :0.00…9842.52 ft (0…3000 m)
Vibration resistance :1 gn 8.4…150 Hz DIN rail | 3.5 mm 5…8.4 Hz DIN rail
Shock resistance :15 gn 11 ms
Resistance to electrostatic discharge :4 kV on contact EN/IEC 61000-4-2 | 8 kV in air EN/IEC 61000-4-2
Resistance to electromagnetic fields :0.91 V/yd (1 V/m) 2…2.7 GHz EN/IEC 61000-4-3 | 9.14 V/yd (10 V/m) 80…2000 MHz EN/IEC 61000-4-3
Resistance to fast transients :1 kV EN/IEC 61000-4-4 I/O) | 1 kV EN/IEC 61000-4-4 shielded cable) | 2 kV EN/IEC 61000-4-4 power lines)
Surge withstand :0.5 kV differential mode EN/IEC 61000-4-5 | 1 kV common mode EN/IEC 61000-4-5
Electromagnetic compatibility :EN/IEC 61000-4-6
Disturbance radiated/conducted :CISPR 11
Packing Units
Unit Type of Package 1 :PCE
Number of Units in Package 1 :1
Package 1 Height :2.95 in (7.500 cm)
Package 1 Width : 3.54 in (9.000 cm)
Package 1 Length : 4.33 in (11.000 cm)
Package 1 Weight :4.20 oz (119.000 g)
Unit Type of Package 2 :S03
Number of Units in Package 2 :36
Package 2 Height :11.81 in (30.000 cm)
Package 2 Width :11.81 in (30.000 cm)
Package 2 Length :15.75 in (40.000 cm)
Package 2 Weight :10.39 lb(US) (4.715 kg)
Shipping weight : 1 Kg