Estimated Lead Time : 9 – 13 Weeks
Manufacturer : B&R
Part Number : X20AI4632
I/O module : 4 analog inputs ±10 V or 0 to 20 mA
B&R ID code : 0x1BA1
Status indicators : I/O function per channel, operating state, module status
Module run/error : Yes, using LED status indicator and software
Inputs : Yes, using LED status indicator and software
Channel type : Yes, using software
Power consumption
Bus : 0.01 W
Internal I/O : 1.5 W
Additional power dissipation caused by actuators (resistive) [W] –
Certifications
CE : Yes
UKCA : Yes
ATEX : Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user’s manual)
FTZÚ 09 ATEX 0083X
UL : cULus E115267
Industrial control equipment
HazLoc : cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV : Temperature: B(0 – 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR : ENV1
KR : Yes
ABS : Yes
EAC : Yes
KC : Yes
Input : ±10 V or 0 to 20 mA, via different terminal connections
Input type : Differential input
Digital converter resolution
Voltage : ±15-bit
Current : 15-bit
Conversion time : 50 μs for all inputs
Output format : INT
Output format Voltage : INT 0x8001 – 0x7FFF / 1 LSB = 0x0001 = 305.176 µV
Output format Current : INT 0x0000 – 0x7FFF / 1 LSB = 0x0001 = 610.352 nA
Input impedance in signal range
Voltaget : 20 MΩ
Currentt : –
Load
Voltaget : –
Currentt : <400 Ω Input protectiont : Protection against wiring with supply voltage Permissible input signal Voltage Max.: ±30 V Current Max.: ±50 mA Output of digital value during overload Undershoot Voltage : 0x8001 Undershoot Current : 0x0000 Overshoot Voltage : 0x7FFF Overshoot Current : 0x7FFF Electrical isolation : Channel isolated from bus Channel not isolated from channel Conversion procedure : SAR Input filter : Hardware - Third-order low-pass filter / cutoff frequency 10 kHz Max. error Voltage Gain : 0.08% Offset : 0.01% Current Gain : 0.08% Offset : 0.02% Max. gain drift Voltage : 0.01%/°C Current : 0.01%/°C Max. offset drift Voltage : 0.001%/°C Current : 0.002%/°C Common-mode rejection DC : 70 dB 50 Hz : 70 dB Common-mode range : ±12 V Crosstalk between channels : <-70 dB Nonlinearity Voltage : <0.01% Nonlinearity Current : <0.015% Insulation voltage between channel and bus : 500 Veff Mounting orientation Horizontal : Yes Mounting orientation Vertical : Yes Installation elevation above sea level 0 to 2000 m : No limitation >2000 m : Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 : IP20
Temperature Operation
Horizontal mounting orientation : -25 to 60°C
Vertical mounting orientation : -25 to 50°C
Derating : See section “Derating”.
Storage : -40 to 85°C
Transport : -40 to 85°C
Note : Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch : 12.5+0.2mm
Operation,Storange&Transport : 5 to 95%, non-condensing
Shipping Weight : 1.5 Kg














Reviews
There are no reviews yet.